What is load balancing?
Load balancing shares one fixed electrical limit, in amps, between several chargers, so that together they never draw more current than the circuit or service allows.
How it works
The charger, or the management system for a group of chargers, divides the limit between the cars that are charging.
While charging is in progress, each charger keeps adapting the maximum current to the limits it has been given (OCPP 2.0.1 Part 2, K02, K04).
Example: a 40 A limit shared by four charging cars gives each 10 A. When two of them finish, the other two can take 20 A each, up to each charger's own maximum.
On AC chargers, the charger sets the maximum current a car may draw through the control pilot signal (OCPP 2.0.1 Part 2, K02). That is the PWM signalling between charger and car defined in IEC 61851-1 and SAE J1772 (OCPP 2.0.1 Appendices, §3.2.21).
Kinds of load balancing
Static
A fixed limit, such as the maximum current of the grid supply, is set once and split between the chargers. OCPP describes this for limits that follow from known physical limits (OCPP 2.0.1 Part 2, K §2.1).
Dynamic
An energy management system or a smart meter on the site limits charging, and the limit can change over time. The charger keeps such a limit as an external constraint (OCPP 2.0.1 Part 2, K §2.4).
Inside one charger
OCPP 1.6 describes load balancing within a charge point that splits a fixed limit, for example the maximum current of its grid supply, between its own connectors (OCPP 1.6, §3.13.4).
From the management system
A management system can set limits with charging profiles. A ChargePointMaxProfile limits all connectors of a charger combined (OCPP 1.6, §3.13.1, §3.13.3).
Single-phase and three-phase
OCPP counts a limit in amps per phase, not as the sum of all phases.
A schedule period can state how many phases may be used for charging; if it does not, three are assumed (OCPP 1.6, §7.12, §7.14).
Ask an electrician first
The limit comes from the circuit or service, and an electrician sets it.
Before you add chargers to a circuit or service, ask a licensed electrician what your local electrical code allows.
What a charger does when it loses its link to the management system matters too. It is explained under smart charging.
How it works in Kinethra
In Connect Business, load balancing works in groups of chargers within one location.
Each group is single-phase or three-phase, with a maximum group current in amps; on a three-phase group the limit applies to each phase.
A group splits current in one of two ways. Proportional shares it equally between active sessions and passes freed capacity on; prioritized serves one priority charger first and shares the rest between the others. The split is recalculated continuously as cars start and stop charging, and no separate meter is needed.
If a charger loses its link to the platform, what it does depends on the algorithm; by default it keeps its last current limit.
In the Connect app, owners of several home chargers can balance them too: in groups, by phase, with a limit in amps and a priority charger.
Sources
- Open Charge Alliance (2017). Open Charge Point Protocol 1.6, edition 2 (opens in a new tab). §3.13.1 Charging profile purposes, §3.13.3, §3.13.4 Smart Charging Use Cases, §7.12 ChargingRateUnitType, §7.14 ChargingSchedulePeriod; accessed 2026-10-22.
- Open Charge Alliance (2025). OCPP 2.0.1 Edition 4, Part 2 – Specification (opens in a new tab). K. Smart Charging: §2.1 Internal Load Balancing, §2.4 External Smart Charging Control Signals, K02 Central Smart Charging, K04 Internal Load Balancing; accessed 2026-10-22.
- Open Charge Alliance (2025). OCPP 2.0.1 Part 2 – Appendices, v1.5 (opens in a new tab). §3.2.21 CPPWMController (IEC 61851-1 / SAE J1772 control pilot); accessed 2026-10-21.
Talk to us about your site
- Tell us about your network.
- Meet a Kinethra specialist.
- Get your chargers live on Kinethra.
- 40,000+ chargers onlineOn the Kinethra platform.
- OCPP 1.6 and 2.0.1Kinethra works with OCPP chargers from any manufacturer.
- No commission on charging revenueKinethra takes none.
We use your details to answer your request. See our Privacy Policy for details.