GroundFailure: what it means and what to do

"Ground fault circuit interrupter has been activated" (OCPP 1.6, §7.6). In OCPP 2.0.1 it appears as the RCD component, Tripped ("Breaker opened (manual reset required)") or Operated (OCPP 2.0.1 Appendices, Chapter 3).

Safety first

This fault involves the charger's electrical protection.

Stop charging and don't touch the charger, its cable or the vehicle connector. If it is safe to do so, switch the charger off at its circuit breaker. Only the charger manufacturer or a licensed electrician should inspect or repair it.

Never clear a ground fault remotely more than once, and never automate a reset loop.

What it means

GroundFailure is a safety signal in every case.

In OCPP 2.0.1 terms, the residual current device (RCD) protects people and equipment by quickly detecting abnormal current flows, usually a sign of an earth fault, in the charging station, the cable or the vehicle during charging (OCPP 2.0.1 Appendices, §3.2.44).

Likely causes

OCPP reports that the protection operated, not why.

Per the RCD definition above, the fault can sit in the charger, the cable or the vehicle, so finding it is a job for the manufacturer or a licensed electrician.

For permanently connected AC charging stations, IEC 62955:2018 covers residual direct current detecting devices (RDC-DD) used in mode 3 charging.

First three checks

  • 1.

    Has this connector reported GroundFailure before?

  • 2.

    One vehicle or several?

  • 3.

    Timing: at plug-in, during charging, or after rain?

What to do

  • Safe remote action

    At most one remote Reset, after a single event, with no one near the equipment, and only if the manufacturer allows it. An RCD reported as Tripped needs a manual reset (OCPP 2.0.1 Appendices, §3.2.44). After any repeat, set the connector Inoperative with ChangeAvailability; this survives reboots (OCPP 1.6, §4.9, §5.2).

  • Dispatch when

    A repeat event, visible damage or water, or a fault that does not clear. Send the manufacturer's technician or a licensed electrician.

  • Do not

    Do not automate resets, and never start a session to test it.

What to tell the customer

"Your charger's safety device detected electricity leaking to ground and switched off to protect you.

Please don't use it until a technician has checked it."

A detection rule to start from

On any GroundFailure (in OCPP 2.0.1, RCD Tripped or Operated): raise priority to high and block automated resets.

On a repeat event: set the connector Inoperative and send an electrician.

Sources

  1. Open Charge Alliance (2017). Open Charge Point Protocol 1.6, edition 2 (opens in a new tab). §4.9 Status Notification, §5.2 Change Availability, §5.14 Reset, §7.6 ChargePointErrorCode.
  2. Open Charge Alliance (2025). OCPP 2.0.1 Part 2 – Appendices, v1.5 (opens in a new tab). Chapter 3, standardized components: §3.2.44 RCD.
  3. International Electrotechnical Commission (2018). IEC 62955:2018, Residual direct current detecting device (RDC-DD) to be used for mode 3 charging of electric vehicles (opens in a new tab). Abstract (scope); accessed 2026-10-22.

Talk to us about your chargers

What happens next

  1. Tell us about your network.
  2. Meet a Kinethra specialist.
  3. Get your chargers live on Kinethra.
  • 40,000+ chargers onlineOn the Kinethra platform.
  • OCPP 1.6 and 2.0.1Kinethra works with OCPP chargers from any manufacturer.
  • No commission on charging revenueKinethra takes none.
  1. 01Contact
  2. 02Business
  3. 03Request

Step 1 of 3

We use your details to answer your request. See our Privacy Policy for details.